International Energy Conservation Code-IECC
2000/2003
Regulatory
Requirements
The
U-factor and solar heat gain coefficient (SHGC) of fenestration
products shall be determined in accordance with National Fenestration
Rating Council Standards NFRC 100 and NFRC 200 respectively by
an accredited, independent laboratory, then labeled and certified
by the manufacturer. Products not meeting these requirements shall
be assigned product values based on defaults values. The default
values typically do not give full credit for energy efficient
performance.
Air
leakage requirements are set at 0.3 cfm/sf for windows and sliding
doors (cubic feet per minute per square foot of window area) and
0.5 cfm/sf for swinging doors. Fenestration systems must be tested
in accordance with AAMA/WDMA 101/I.S.2.
Residential
Buildings
The
IECC has two compliance paths for residential buildings: A Simplified
Prescriptive path and a Component Approach.
Simplified
Prescriptive Requirements
Fenestration (glazing) area cannot
exceed 15% of the gross wall area for one and two family dwellings.
Opaque exterior doors cannot
exceed a maximum U-factor of 0.35; however one door is exempt
from the requirement.
The code has a table that defines
17 climate zones based on Heating Degree Days with minimum fenestration
performance U-factors and SHGC requirements. These requirements
can be simplified as follows:
Heating
Degree Days |
U-factor
(max) |
SHGC
(max) |
0
– 499 |
NR
|
0.40
|
500
- 999 |
0.9
|
0.40
|
1,000
– 1,999 |
0.75
|
0.40
|
2,000
– 2,499 |
0.65
|
0.40
|
2,500
– 2,999 |
0.6
|
0.40
|
3,000
– 3,499 |
0.55
|
0.40
|
3,500
– 3,999 |
0.50
|
NR
|
4,000
– 5,499 |
0.45
|
NR
|
5,500
– 5,999 |
0.4
|
NR
|
6,000
– 12,999 |
0.35
|
NR
|
Note
that envelope performance criteria change for each climate zone.
NR
– No Requirement.
Component
Approach
This
method for code compliance utilizes the same seventeen climate
zones, but does not restrict fenestration area to 15% of the gross
wall area; rather, it provides tables for 8%, 12%, 15%, 18%, 20%
and 25% fenestration area. In addition,
The requirement remains for an
SHGC = 0.40 for all climate zones with heating degree-days below
3,500.
U-factor requirements become
more restrictive as the fenestration area increases. For example,
if a residence only has 12% fenestration area, the U-factor requirements
only go down to U < 0.40; while a residence with 25% fenestration
area can require a U-factor < 0.25.
Up to one percent of the window
area is also exempt from meeting the fenestration U-factor requirement
For
the first time, window replacement and room additions were also
addressed in an energy code. The 2000 IECC established the following
table of prescriptive requirements for these products:
Heating
Degree Days |
U-factor
|
SHGC
|
0
– 1,999 |
0.75
|
0.40
|
2,000
– 3,999 |
0.5
|
0.40
|
4,000
– 5,999 |
0.4
|
NR
|
6,000
– 8,499 |
0.35
|
NR
|
8,500
– 12,999 |
0.35
|
NR
|
Performance
Approach
This method allows the designer to model the building using prescriptive
method compliant components creating a "standard" design
and an associated energy budget. The designer then may model
the building again trading off components against one another
as long as the proposed design's energy budget is less than the
standard design's energy budget. Some of the fenestration
limitations on this approach are:
- Standard design window area = 18% of the proposed design conditioned
floor area
- Standard design U factor maximums are prescribed (table 402.2.1.2
in Chapter 4)
- Skylights are not included in the standard design computation
- Standard design SHGC < 0.4 if HDD < 3,500
- Standard Design SHGC < 0.68 if HDD > 3,500
- Standard and proposed design interior shading factors must
be equal (0.7 summer, 0.9 winter)
Commercial
Buildings
The
IECC has two compliance paths for commercial buildings. One is
simply a reference to ASHRAE 90.1-99. The other is “Design By
Acceptable Practice.”
Building
envelope requirements are subdivided into seventeen climate zones
and into four fenestration area tables including:
Fenestration area 10% or less
than above grade wall area;
Fenestration area between 10%
and 25% of the above grade wall area;
Fenestration area between 25%
and 40% of the above grade wall area; and
Fenestration area between 40%
and 50% of the above grade wall area.
U-factors
for fenestration products range as low as 0.40 and SHGC requirements
as low as 0.30. Credit is given for overhangs that help somewhat
to minimize the strict SHGC requirements. Energy use in commercial
buildings is typically dominated by cooling loads so lower SHGC
fenestration products ratings are desirable.
|