|
2006
IECC
The 2006 changes (compared
to IECC 2003), include:
- New climate basis: - strictly geographical (no more HDD)
-
- fewer zones (more homogeneity within jurisdictions)
-
- better
climate coverage (zones based on more than HDD)
-
- Residential / Commercial use the same climate
zones
- Single family and multy family consolidated
- Envelope requirements independent of window-wall ratio (except
in perfortmance path)
- Performance path closer to prescriptive
- New "trade-off" limits for glazing U-Factor and
SHGC
Chapter 1:
ADMINISTRATION
Regulatory
Requirements (102.1.3)
U-Factors
and Solar Heat Gain Coefficient (SHGC) of fenestration products
(windows, doors and skylights) shall be determined in accordance
with NFRC 100 and NFRC 200 respectively, by an accredited, independent
laboratory, and labeled and certified by the manufacturer. Products
lacking such labels, shall be assigned default values (Table 102.1.3:
1, 2 and 3). The default values typically do not give full credit
for energy efficient performance.
Chapter
4: RESIDENTIAL ENERGY EFFICIENCY
Fenestration
Air Leakage( 402.4.2. - mandatory):
Air
leakage requirements are set at 0.3 cfm/sf for windows and sliding
doors (cubic feet per minute per square foot of window area) and
0.5 cfm/sf for swinging doors. Fenestration systems must be tested
in accordance with NFRC 400 or AAMA/WDMA/CSA 101/I.S.2/A440, by
an accredited, independent laboratory and listed and labeled by
the manufacturer.
Exceptions: Site built windows, skylights
and doors.
Prescriptive
requirements (402.1.1) - by climate zone are shown
below:
Table
402.1.1 in the 2006 IECC
| Climate
Zone |
Fenestration
U-Factor |
Fenestration
SHGC |
1 |
1.20 |
0.40 |
2 |
0.75 |
0.40 |
3 |
0.65 |
0.40 |
4 except
marine |
0.40 |
None |
5 to 8
& marine 4 |
0.35 |
None |
Click
here to see the corresponding climate map.
Total UA alternative
(402.1.4)
If the total building
thermal envelope UA (sum of U-factor times assembly area) is less
than or equal to the total UA resulting from using the U-factors
in Table 402.1.3 (see below, multiplied by the same assembly area
as in the proposed building), the building shall be considered
in compliance with Table 402.1.1 (above). The UA calculation shall
be done using a method consistent with the ASHRAE Handbook of
Fundamentals and shall include the thermal bridging effects of
framing materials. The SHGC requirements shall be met in addition
to UA compliance.
Table 402.1.3 in 2006 IECC
Climate
Zone |
|
Skylight
U Factor |
| 1 |
1.20 |
0.75 |
2 |
0.75 |
0.75 |
3 |
0.65 |
0.65 |
4 except
marine |
0.40 |
0.60 |
5 &
marine 4 |
0.35 |
0.60 |
6 |
0.35 |
0.60 |
7 &
8 |
0.35 |
0.60 |
Simulated Performance
Alternative (404)
Compliance based on
simulated energy performancerequires that a proposed residence
(proposed design) be shown to have an annual energy cost that
is less than or equal to the annual energy cost of the standard
reference design. Some of the fenestration limitations on this
approach are (trade off limitations):
- U-Factor < 0.48 in zones 4 and 5; and < 0.40 in zones
6 to 8 (vertical fenestration)
- U-Factor < 0.75 in zones 4 to 8 (skylights)
- SHGC < 0.50 in zones 1 to 3
Note, the 2006 IECC performance analysis
now uses energy cost, not consumption,
for comparison (similar to ASHRAE's methods.) This means that
electricity use is penalized since it is an expensive fuel.
For fenestration, this means that SHGC may be more heavily credited
in the design since a SHGC reduction will result in reduced cooling
cost which is electrically driven. This fact may allow the designer
to trade off against other components more easily.
|