NFRC - National Fenestration Rating Council
 
WE'RE CHANGING THE WAY AMERICA SHOPS
FOR WINDOWS, DOORS AND SKYLIGHTS
Home  |  Contact Us  |  Community Login
<< Back
About NFRC Toggle Menu
Get Your Product Certified Toggle Menu
NFRC Certification Program Participant Listing
NFRC Certified Products Directory Toggle Menu
NFRC Independent Verification Program (IVP)
ANS Standards Development
NFRC Component Modeling Approach Program (CMA)
Industry News
Press Room Toggle Menu
Fenestration Facts Toggle Menu
NFRC and Energy Codes Toggle Menu
Support NFRC: Membership Information Toggle Menu
Helpful Links
FAQs
NFRC COMMUNITY NFRC Community
Member Tools Toggle Menu
Program Participant Tools Toggle Menu
NFRC Documents and Resources Toggle Menu
Submit Thermophysical Properties
Submit Optical Properties
Committees, Subcomittees,Task Groups and Board Toggle Menu
Meeting Information Toggle Menu
Discussion Boards Toggle Menu
Certified Products Database

2009 IECC

Chapter 3: Climate Zones

Regulatory Requirements (303.1.3)

U-Factors and Solar Heat Gain Coefficient (SHGC) of fenestration products (windows, doors and skylights) shall be determined in accordance with NFRC 100 and NFRC 200 respectively, by an accredited, independent laboratory, and labeled and certified by the manufacturer. Products lacking such labels, shall be assigned default values (Table 301.1.3: 1, 2). The default values typically do not give full credit for energy efficient performance.

Chapter 4: RESIDENTIAL ENERGY EFFICIENCY

Fenestration Air Leakage( 402.4.4. - mandatory):

Air leakage requirements are set at 0.3 cfm/sf for windows and sliding doors (cubic feet per minute per square foot of window area) and 0.5 cfm/sf for swinging doors. Fenestration systems must be tested in accordance with NFRC 400 or AAMA/WDMA/CSA 101/I.S.2/A440, by an accredited, independent laboratory and listed and labeled by the manufacturer.    Exceptions: Site built windows, skylights and doors.

Prescriptive requirements (402.1.1) - by climate zone are shown below:

                       Table 402.1.1 in the 2009 IECC

Climate Zone Fenestration U-Factor Fenestration SHGC
1 1.20 0.30
2 0.65 0.30
3 0.50 0.30
4-8 0.35 None

Click here to see the corresponding climate map.

Glazed Fenestration Exemption 402.3.3.)

Up to 15 square feet (1.4m2) of glazed fenestration per dwelling unit shall be permitted to be exempt from U-factor and SHGC requirements in Section 402.1.1. This exemption shall not apply to the U-factor alternative approach in Section 402.1.3 and the Total UA alternative in Section 402.1.4.

Total UA alternative (402.1.4)

If the total building thermal envelope UA (sum of U-factor times assembly area) is less than or equal to the total UA resulting from using the U-factors in Table 402.1.3 (see below, multiplied by the same assembly area as in the proposed building), the building shall be considered in compliance with Table 402.1.1 (above). The UA calculation shall be done using a method consistent with the ASHRAE Handbook of Fundamentals and shall include the thermal bridging effects of framing materials. The SHGC requirements shall be met in addition to UA compliance.                                            

                               Table 402.1.3 in 2009 IECC

Climate Zone

Fenestration

U-Factor

Skylight U Factor
1    1.20 0.75
2 0.65 0.75
3 0.50 0.65
4-8 0.35 0.60

Simulated Performance Alternative (405.2)

Mandatory requirements. Compliance with this section
requires that the mandatory provisions identified in Section
401.2 be met.